Product Highlights
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
DSE871x max @ 24 V = 70 mA
DSE871x max @ 12 V = 140 mA
OUTPUTS
AUXILLARY OUTPUTS C & D
2 A DC at supply voltage