Product Highlights
Key Features
Key Benefits
- Additional Features
- Customisable status screens.
- Multiple date & time scheduler.
- Charge alternator failure alarm.
- CAN engine manual speed control.
- Manual fuel pump control.
- Engine exerciser.
- kW & kV Ar overload protection.
- Reverse power (kW & kV Ar) protection.
- Unbalanced load protection.
- USB connectivity.
- Backed-up real time clock.
- Configurable Gencomm pages.
- SMS messaging start & stop functionality.
- Modem diagnostic display screens.
- Remote display support (max 3 units).
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
340 mA at 12 V, 160 mA at 24 V
MAXIMUM STANDBY CURRENT
160 mA at 12 V, 80 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A 250 V (Volt free)
AUXILIARY OUTPUTS E,F,G,H
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)