Product Highlights
Key Features
Key Benefits
- Additional Features
- Hours counter.
- Multiple display parameters.
- Extensive configuration options.
- Engine maintenance alarms (3).
- Engine monitoring & protection.
- Engine hours counter.
- Engine pre-heat.
- Run time scheduler.
- Battery voltage monitoring.
- Start on low battery.
- Backed-up real time clock.
- Manual fuel pump control.
Specification
DC SUPPLY
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
290 mA at 12 V, 140 mA at 24 V
MAXIMUM STANDBY CURRENT
75 mA at 12 V, 40 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V – 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A 250 V (Volt free)
AUXILIARY OUTPUTS E, F, G & H
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V – 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)