Two-part solution.
Allows mains (utility) and bus breakers to be located up to 1.2km apart.
Multiple mains (utility) capability (with additional module).
To monitor alternative mains supplies to ensure generator power is supplied at the exact time required.
Mains (Utility) failure detection, mains (utility) power monitoring (kW, kV Ar, kV A & pf) monitoring, mains (utility) decoupling protection, mains (utility) kW export protection.
Gives full mains (utility) back-up and provides no break synchronisation that includes peak lopping and peak shaving options with mains (utility) power monitoring.
Configurable inputs/outputs (11/8).
Provides multiple installation options.
kW & kV Ar load sharing.
Provides controlled power delivery.
Remote communications (RS232, RS485 x2, Ethernet).
Provides secure and simple off site monitoring. All ports are continuously active.
Configurable event log (250).
Provides access to historical alarms and operational status.
Integral PLC editor.
Ensures additional applications are easily integrated into the system.
Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Provides clear accurate power measurement information.
Data logging (USB Memory Stick).
Provides current and historical status information.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Tier 4 CAN engine support.
Ensures the control module can be used with the latest in modern electronic engine technology.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
340 mA at 12 V, 160 mA at 24 V
MAXIMUM STANDBY CURRENT
160 mA at 12 V, 80 mA at 24 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
LOAD
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUTS C & D
8 A at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H, I & J
2 A DC at supply voltage