32-set synchronisation.
Offers optimum flexibility for system expansion.
Configurable inputs/outputs (11/8).
Provides multiple installation options.
Dead bus sensing.
Provides rapid power delivery on multi-set systems.
Remote communications (RS232, RS485, Ethernet).
Provides secure and simple off site monitoring. All ports are continuously active.
Direct governor control.
Eliminates the requirement for external control equipment.
kW & kV Ar load sharing.
Provides controlled power delivery.
Configurable event log (250).
Provides access to historical alarms and operational status.
Integral PLC editor.
Ensures additional applications are easily integrated into the system.
Load switching, load shedding & dummy load outputs.
Allows load options and dummy load requirements to be independently controlled.
Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Provides clear accurate power measurement information.
Data logging (USB Memory Stick).
Provides current and historical status information.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Tier 4 CAN engine support.
Ensures the control module can be used with the latest in modern electronic engine technology.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
460 mA at 12 V, 245 mA at 24 V
MAXIMUM STANDBY CURRENT
375 mA at 12 V, 200 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage
GENERATOR & BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
BUILT-IN GOVERNOR CONTROL
MINIMUM LOAD IMPEDANCE
1000Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
+/- 10 V DC
Fully isolated
BUILT-IN AVR CONTROL
MINIMUM LOAD IMPEDANCE1000Ω
Fully isolated
GAIN VOLTAGE0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE+/- 10 V DC
Fully isolated