Key Features
Key Benefits
CAN and magnetic pick-up sensing.
Makes the module ideal for standard and electronic engine applications.
Configurable inputs/outputs (11/8).
Provides multiple installation options.
Fuel usage monitor and low level alarms.
Tracks the amount of fuel being used and sounds an alarm if over/under fuel use is detected.
Remote communications (RS232, RS485, Ethernet, Modbus, RTU/TCP).
Provides secure and simple off site monitoring. All ports are continuously active.
Configurable event log (250).
Provides access to historical alarms and operational status.
Integral PLC editor.
Ensures additional applications are easily integrated into the system.
Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Provides clear accurate power measurement information.
Load switching, load shedding & dummy load outputs.
Allows load options and dummy load requirements to be independently controlled.
Data logging (USB Memory Stick).
Provides current and historical status information.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Tier 4 CAN engine support.
Ensures the control module can be used with the latest in modern electronic engine technology.
- Additional Features
- Mains (Utility) failure detection.
- Unbalanced load transfer.
- Voltage measurement.
- Dedicated load test button.
-
- kW overload alarms.
- Exercise timer.
- Multiple language options.
-
- Configurable timers & alarms.
- Configurable start/stop timers.
- Configurable maintenance alarms (3).
-
- Charge alternator failure alarm.
- Speed & fuel pump control.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
260 mA at 12 V, 130 mA at 24 V
MAXIMUM STANDBY CURRENT
120 mA at 12 V, 65 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)