Key Features
Key Benefits
6 configurable DC outputs.
Provides multiple installation options.
4 configurable analogue/digital inputs.
Provides multiple installation options.
8 configurable digital inputs.
Provides multiple installation options.
3-phase generator and mains (utility) sensing.
Provides true generator and mains (utility) sensing.
Automatic load transfer control.
Ensures the load can be transferred manually/automatically between mains (utility) and generator power.
Generator & mains current and power monitoring.
Provides convenience of monitoring and protection of the generator or monitoring of the load current.
Internal PLC editor.
Adds increased flexibility to the product.
Breaker control buttons on front fascia.
Simple breaker control at the touch of a button.
Fuel and start outputs configurable when using CAN.
Provides multiple installation options.
Tier 4 ECO engine support including exhaust fluids & filters.
Ensures the control module can be used with the latest in modern electronic engine technology.
DSENet expansion compatibility.
Offers optimum flexibility for system expansion.
Data logging facility
Data can be used for gathering system information.
Configurable event log (100).
Provides access to historical alarms and operational status.
CAN, MPU & alternator speed sensing (selectable depending on engine type).
Ensures the module can be used with a wide number of engine types.
Support for 0-10 V & 4-20mA oil pressure senders.
Provides flexibility for use with multiple sensors and engine types.
Customisable power up text and images
Allows the installer to change the logo and text on module power up.
Five key menu navigation
Provides comprehensive front panel module control.
Backed-up real time clock.
Maintains the settings of the module when power is removed.
Fuel usage monitor and low level alarms.
Provides information on fuel status at all times.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for up to 1 minute
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
260 mA at 12 V, 150 mA at 24 V
MAXIMUM STANDBY CURRENT
145 mA at 12 V, 85 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICKUP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
INPUTS
DIGITAL INPUTS A to H
Negative switching
ANALOGUE INPUTS A & D
Configurable as:
Negative switching digital input
0 V to 10 V sensor
4 mA to 20 mA sensor
Resistive sensor
ANALOGUE INPUTS B & C
Configurable as:
Negative switching digital input
Resistive sensor
OUTPUTS
OUTPUT A & B (FUEL & START)
15 A DC at supply voltage
AUXILIARY OUTPUTS C, D, E, F, G & H
2 A DC at supply voltage