Front panel key switch.
Ensures the generator can only be operated when the key is used.
Standard engine and electronic CANbus variants.
Instant integration with both standard and modern electronically controlled engines.
Configurable inputs/outputs (6 digital inputs/4 outputs – 2 outputs configurable on magnetic pick-up variant).
Provides multiple installation options.
Remote start input.
Provides a simple connection to operate the generator from a remote location.
Comprehensive display parameters.
Provides instant notification of generator voltage, generator frequency, battery voltage, engine speed and run hours via one button navigation.
Engine pre-heat.
Warms the engine to a safe temperature at start-up to increase engine life.
Configurable timers & alarms.
Provides flexibility to suit individual operating requirements.
Large back-lit icon LCD display.
Displays information to the operator in a clear and concise format.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
CHARGE FAIL/ EXCITATION
8 V to 35 V fixed power source 2.5 W
NOMINAL STANDBY CURRENT
35 mA at 12 V, 30 mA at 24 V
MAXIMUM OPERATING CURRENT
55 mA at 12 V, 60 mA at 24 V
OUTPUTS
OUTPUT A (FUEL)
2 A DC at supply voltage
OUTPUT B (START)
2 A DC at supply voltage
AUXILIARY OUTPUTS C,D
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V - 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)